FKN12-12/FK (RN) 12-12RD Indoor High Pressure Gas Load Switch

Short Description:


Product Detail

Product Tags

Overview

FKN12 compressed air load switch, FKRN12 series compressed air load switch-fuse combination electrical appliances, suitable for 12KV and below three-phase power distribution system, as the control and protection of transformers, cables, overhead lines and other power equipment; especially suitable for Terminal substations and box-type substations of urban power grids and rural power grids. And it is suitable for control and protection of ring network and double radiation power supply unit.
FKN12 series pneumatic load switch can switch load current and overload current.
FKRN12 series compressor-type load switch-fuse combination can switch load current, overload current, and break circuit short-circuit current.

Conditions of Use

◆The upper limit of ambient air temperature: +40°C lower limit -25°C
◆The altitude does not exceed 1000m;
◆The daily average of relative humidity is not more than 95%, and the monthly average is not more than 90%.
◆Earthquake intensity does not exceed 8 degrees;
◆A place without fire, explosion hazard, chemical corrosion and severe vibration;
◆Pollution level: ll

Main Feature

◆Load switch, grounding switch, fuse and mechanism are on one frame, which can be flexibly combined, compact in structure, small in size, and easy to install;
◆Fractures are arranged in direct-acting mode, with high dynamic and thermal stable current parameters, and the operation can be completed at one time;
◆With static contact insulation cover, the ring network cabinet is isolated in structure, eliminating the need for interphase insulation partitions and fracture insulation boards, which can prevent arc short-circuit accidents in the cabinet;
◆It has a unique valve structure. After the load switch is opened, the valve automatically isolates the fracture and has good protection performance;
◆There is a reliable mechanical locking device between the load switch, the grounding switch and the fuse, which meets the requirements of “five preventions”;
◆There are two forms of manual operation and electric operation of AC and DC dual-purpose operation power supply, which is convenient to realize the power system; “three remote” requirements.